This paper proposes an Optimal Fuzzy-Proportional-integral-derivative (PID) controller tuned by a Hybrid grey wolf optimizer–particle swarm optimization (Hybrid GWO–PSO) algorithm for Automatic generation control (AGC) of a two-area interconnected power system comprising a thermal reheat and a hydropower system linked through a tie-line. The proposed controller integrates an adaptive fuzzy inference mechanism that adjusts the effective PID gains according to the instantaneous Area control error (ACE) and its rate of change, while the Hybrid GWO–PSO algorithm optimizes the controller parameters by minimizing the Integral of time-multiplied absolute error (ITAE) cost function. Under a 0.1 p.u. Step load disturbance (SLD), the proposed controller attains the lowest ITAE of 11.0519, corresponding to improvements of approximately 90.72%, 58.51%, and 32.43% over the Proportional-integral (PI), PID, and Fuzzy-PID controllers, respectively, together with superior overshoot, undershoot, and settling-time performance. A statistical analysis over 30 independent trials further validates its convergence consistency, yielding a mean ITAE of 12.0201 with a standard deviation of merely 0.4397. When the tuned parameters are directly applied to a randomly varying load profile without re-optimization, the proposed controller again attains the lowest ITAE of 201.6646, substantiating its robustness against unpredictable load fluctuations and confirming its viability for practical AGC implementation.